  • Air torque position damper ...
    Bikić, Siniša; Uzelac, Dušan; Bukurov, Maša; Todorović, Bogoljub; Tašin, Slobodan

    Energy and buildings, 07/2015, Volume: 99
    Journal Article

    •Energy consumption of the air torque position dampers was studied.•Four possible types of dampers with non-cascading blades were considered.•Damper with two blades (only one measuring blade) has minimum energy consumption.•This damper has notably lower energy consumption compared to other types of damper. The damper used for the control of airflow in heating, ventilation and air conditioning systems can constructively be adapted to measure the air velocity with its moment characteristic. It is a device that indirectly determines the air velocity by measuring the position of the blades and the air stream moment acting on it. The subject of this paper is energy consumption of the air torque position damper depending on its structure. The aim is to compare the energy consumption of four possible types of dampers with non-cascading blades: with one blade, with two cross-guided blades, with two parallels-guided blades and with two blades, one of which is a measuring blade and the other remains fixed in horizontal position. The case when there is a straight section of a duct both in front of and behind the damper was considered. Adequacy of the existing mathematical model and energy consumption for all four types of dampers was determined experimentally. It was found that the damper with two blades of which one is a measuring blade and other remains fixed in horizontal position had minimal energy consumption.