ALL libraries (COBIB.SI union bibliographic/catalogue database)
  • Influence of the network reconfiguration on the voltage flicker level
    Voršič, Jože ; Horvat, Miran ; Orgulan, Andrej
    Electric arc furnace at "Železarna Ravne" steel plant, due to increase of production, causes annoying voltage fluctuation, which appears as disturbed lighting. Paper presents the results of the ... flicker level measurements and influence of the network reconfiguration in the point of common coupling. Reconfiguration was analysed first with simulation and afterwards in site. Results showing the relation between the short-circuit power and the flicker level are presented.
    Type of material - conference contribution
    Publish date - 1998
    Language - english
    COBISS.SI-ID - 3668502