DIKUL - logo
Centralna tehniška knjižnica Univerze v Ljubljani (CTK)
  • A 6.3 kV vacuum breaker model for ATP simulations
    Kosmač, Janko, 1966- ; Žunko, Peter
    A model of medium voltage vacuum breaker was developed by using new powerful TACS MODELS. The new model includes arc voltage characteristic, calculation of chopping current with known di/dt, ... dielectric breakdown voltage characteristic and contact separation dynamics. Influences of a differently loaded induction motor cable-connected to 6.3 kV bus on overvoltages were calculated. This approach provides valuable information to enigineers constructing metal enclosed switchgear and other users who are going to install vacuum breakers in medium voltage networks.
    Vir: Proceedings (Str. 39-44)
    Vrsta gradiva - prispevek na konferenci
    Leto - 1993
    Jezik - angleški
    COBISS.SI-ID - 18608133

vir: Proceedings (Str. 39-44)