UP - logo
ALL libraries (COBIB.SI union bibliographic/catalogue database)
  • Analysis of the network protection devices action connected with the Krško NPP operation safety
    Omahen, Pavel ; Štruc, Silvo
    The example of failure that took place in Zagreb on 30 March 1995, has been investigated in order to obtain appropriate answers to the unexpected electric power system (EPS) response and consecutive ... outage of the Krško nuclear power plant (NPP). The analysis has been made of particular operating and stability conditions, related to the functioning of distance relay line protection. Using a consequent simulation model of the EPS (European intercon.) under specified fault condition, the research of EPS operation (relay action) and stability has been done. The appropriate simulation results have been compared to the available measured data which had been collected by the SOREL on-line data acquisition system. In the end, a precise proposal for measures to be taken with the target of achieving the foreseen and expected operation of the EPS equipment that effects operation of the krško NPP is given.
    Source: Proceedings (Str. 394-401)
    Type of material - conference contribution
    Publish date - 1995
    Language - english
    COBISS.SI-ID - 17952773

source: Proceedings (Str. 394-401)