Energy renovations of the building stock are a paramount objective of the European Union (EU) to combat climate change. A tool for renovation progress monitoring is energy performance certificate ...(EPC) labelling. The present study tested the effect of different EPC label classifications on a national database, which comprises ~25,000 EPC values from apartment buildings, detached houses, office buildings, and educational, commercial, and service buildings. Analysing the EPC classes labelling resulting from four different EU methods, we estimated the annual renovation rates, costs, energy savings, and CO2 emissions reduction that would affect the national building stock if each of them was adopted, to fulfil the European Climate Target Plan by the year 2033. The ISO 52003-1:2017 two-point and one-point methods determined a very uneven distribution of renovation rates, from 0.45% to ~9%. Conversely, the Directive 15% recently proposed in COM/2021/802 with uniform rates determined smaller differences and standard deviation, not pushing renovations above 3.70%, namely a rate that once fine-tuned can stimulate realistic, yet effective renovation campaigns. The major differences in renovation rates provided by the studied methods show the need for a harmonized strategy such as the Directive proposal to enable achievement of European targets.
During the rapid rise in COVID-19 illnesses and deaths globally, and notwithstanding recommended precautions, questions are voiced about routes of transmission for this pandemic disease. Inhaling ...small airborne droplets is probable as a third route of infection, in addition to more widely recognized transmission via larger respiratory droplets and direct contact with infected people or contaminated surfaces. While uncertainties remain regarding the relative contributions of the different transmission pathways, we argue that existing evidence is sufficiently strong to warrant engineering controls targeting airborne transmission as part of an overall strategy to limit infection risk indoors. Appropriate building engineering controls include sufficient and effective ventilation, possibly enhanced by particle filtration and air disinfection, avoiding air recirculation and avoiding overcrowding. Often, such measures can be easily implemented and without much cost, but if only they are recognised as significant in contributing to infection control goals. We believe that the use of engineering controls in public buildings, including hospitals, shops, offices, schools, kindergartens, libraries, restaurants, cruise ships, elevators, conference rooms or public transport, in parallel with effective application of other controls (including isolation and quarantine, social distancing and hand hygiene), would be an additional important measure globally to reduce the likelihood of transmission and thereby protect healthcare workers, patients and the general public.
A new design method is proposed to calculate outdoor air ventilation rates to control respiratory infection risk in indoor spaces. We propose to use this method in future ventilation standards to ...complement existing ventilation criteria based on the perceived air quality and pollutant removal. The proposed method makes it possible to calculate the required ventilation rate at a given probability of infection and quanta emission rate. Present work used quanta emission rates for SARS-CoV-2 and consequently the method can be applied for other respiratory viruses with available quanta data. The method was applied to case studies representing typical rooms in public buildings. To reduce the probability of infection, the total airflow rate per infectious person revealed to be the most important parameter to reduce the infection risk. Category I ventilation rate prescribed in the EN 16798-1 standard satisfied many but not all type of spaces examined. The required ventilation rates started from about 80 L/s per room. Large variations between the results for the selected case studies made it impossible to provide a simple rule for estimating the required ventilation rates. Consequently, we conclude that to design rooms with a low infection risk the newly developed ventilation design method must be used.
•New design method for respiratory infection risk-based ventilation rates•Provides the required ventilation rate at a given probability and quanta emission•Estimates a low-risk ventilation rate from the event reproduction number•Case studies show ventilation rates starting from about 80 L/s per room•Is proposed for ventilation standards to complement existing ventilation criteria
Abstract
With a modified version of the Wells-Riley model, we simulated the size distribution and dynamics of five airborne viruses (measles, influenza, SARS-CoV-2, human rhinovirus, and adenovirus) ...emitted from a speaking person in a typical residential setting over a relative humidity (RH) range of 20–80% and air temperature of 20–25 °C. Besides the size transformation of virus-containing droplets due to evaporation, respiratory absorption, and then removal by gravitational settling, the modified model also considered the removal mechanism by ventilation. The trend and magnitude of RH impact depended on the respiratory virus. For rhinovirus and adenovirus humidifying the indoor air from 20/30 to 50% will be increasing the relative infection risk, however, this relative infection risk increase will be negligible for rhinovirus and weak for adenovirus. Humidification will have a potential benefit in decreasing the infection risk only for influenza when there is a large infection risk decrease for humidifying from 20 to 50%. Regardless of the dry solution composition, humidification will overall increase the infection risk via long-range airborne transmission of SARS-CoV-2. Compared to humidification at a constant ventilation rate, increasing the ventilation rate to moderate levels 0.5 → 2.0 h
−1
will have a more beneficial infection risk decrease for all viruses except for influenza. Increasing the ventilation rate from low values of 0.5 h
−1
to higher levels of 6 h
−1
will have a dominating effect on reducing the infection risk regardless of virus type.
The comparison of building energy efficiency in different climates is a growing issue. Unique structural solutions will not ensure the same energy use, but the differences also remain if cost-optimal ...solutions are applied. This study developed a new equation for the assessment of building envelope optimal insulation in different climates for office buildings. The developed method suggests determining actual degree days from simulated heating energy need and the thermal conductance of a building, avoiding in such a way the use of a base temperature. The method was tested in four climates and validated against cost-optimal solutions solved with optimization. The accuracy of the method was assessed with sensitivity analyses of key parameters such as window-to-wall ratios (WWRs), window g-values, costs of heating, and electricity. These results showed that the existing square root equation overestimated the climate difference effect so that the calculation from the cold climate U-value resulted in less insulation than cost-optimal in warmer climates. Parametric analyses revealed that the power value of 0.2 remarkably improved the accuracy as well as performance worked well in all cases and can be recommended as a default value. Sensitivity analyses with a broad range of energy costs and window parameters revealed that the developed equation resulted in maximum 5% underestimation and maximum 7% overestimation of an average area-weighted optimal U-value of building envelope in another climate. The developed method allows objectively to compare optimal insulation of the building envelope in different climates. The method is easy to apply for energy performance comparison of similar buildings in different climates and also for energy performance requirements comparison.
Space Heating (SH) substations in District Heating-based (DH) systems are typically dimensioned at the design outdoor temperature without accounting for internal and solar heat gains. In residential ...buildings, the total required DH power typically also includes the need for Domestic Hot Water (DHW). This practice results in oversized substations and high DH design flow rates, which, due to heat gains and building thermal mass utilization in building operation, rarely, if ever, occur. Modern buildings maintain the desired indoor temperature with lower heating power by controlling the SH supply temperature with an outdoor-air-dependent heating curve and heating water flow with room unit thermostats. Applying a dynamic heating control algorithm can be considered one option to reduce the required DH power and optimize the DH network. Another possibility to decrease the needed power is controlling the DH flow by prioritizing DHW production and limiting the DH flow for SH. This study proposed a novel sizing method for the DH substation that quantifies the effects of dynamic control and flow limiters. Building models with detailed hydronic plants, accounting for internal heat gains, and using conventional and dynamic heating controls were developed in the IDA Indoor Climate and Energy simulation tool. The results show a potential DH side power reduction of up to 25%.
Single room ventilation units with heat recovery is one of the ventilation solutions that have been used in renovated residential buildings in Estonia. In multi-story buildings, especially in a cold ...climate, the performance of units is affected by the stack effect and wind-induced pressure differences between the indoor and the outdoor air. Renovation of the building envelope improves air tightness and the impact of the pressure conditions is amplified. The aim of this study was to predict the air pressure conditions in typical renovated multi-story apartment buildings and to analyze the performance of room-based ventilation units. The field measurements of air pressure differences in a renovated 5-story apartment building during the winter season were conducted and the results were used to simulate whole-year pressure conditions with IDA-ICE software. Performance of two types of single room ventilation units were measured in the laboratory and their suitability as ventilation renovation solutions was assessed with simulations. The results show that one unit stopped its operation as a heat recovery ventilator. In order to ensure satisfactory indoor climate and heat recovery using wall mounted units the pressure difference values were determined and proposed for correct design.
•Indoor air quality (IAQ) of schools with/without reported IAQ complaints were studied.•Indoor climate questionnaires were used to verify the categorisation of schools.•More cultivable airborne ...microbes were found in schools with reported IAQ complaints.•Trichoderma was found only in the schools with reported IAQ complaints.•Other IAQ-related measurements were unable to uncover reasons for IAQ complaints.
Reported indoor air quality (IAQ) complaints are common even in relatively new or renovated school buildings in Finland. However, detecting the causes for complaints with commonly used indoor air measurements is difficult. This study presents data on perceived and measured IAQ in six comprehensive school buildings in Finland. The aim of this study was to discover the possible differences of perceived and measured IAQ between schools with reported IAQ complaints and schools without reported IAQ complaints. The initial categorisation of schools with (‘problematic schools’) and without (‘comparison schools’) complaints was ensured via a validated indoor climate survey and a recently developed online questionnaire, which were completed by 186 teachers and 1268 students from the six schools. IAQ measurements of physical parameters, gaseous pollutants, particulate matter and bioaerosols were conducted in four problematic school buildings (26 classrooms) and two comparison school buildings (12 classrooms). Using air sampling as well as exhaust air filters and classroom settled dust to detect the presence of elevated concentrations of airborne cultivable microbes and pathogenic, toxigenic and mycoparasitic Trichoderma strains were the most indicative methods in distinguishing problematic schools from comparison schools. Other IAQ-related measurements did not detect clear differences between problematic and comparison schools, as the concentration levels were very low. The results indicate that the complaints reported by occupants could have been related to excess moisture or mould problems that had not been found or repaired. Ventilation pressure condition investigations and simultaneous exhaust and supply air filter dust culture should be addressed precisely in future studies.
Finland has approximately 150,000 oil-heated private homes. In 2020, the Finnish government launched subsidies for private homeowner energy renovations. In this study, we examine the impact of two ...new energy renovation subsidies, the ELY grant and the ARA grant, from an energy efficiency point of view. Data from these subsidies reveal that a typical energy renovation case is a building from the 1970s where the oil boiler is replaced with an air-to-water heat pump. With additional data from the Finnish Energy certificate registry, a reference 1970s house is constructed and modelled in the building simulation programme, IDA ICE 4.8. Combinations of several renovation measures are simulated: air-to-water heat pump, ground-source heat pump, ventilation heat recovery and improved insulation. We found that resorting mainly to air-to-water heat pumps is not the most energy-effective solution. Ground-source heat pumps deliver a more significant reduction in delivered energy, especially with additional measures on insulation and heat recovery. Ground-source heat pumps also demand slightly less power than air-to-water heat pumps. Onsite solar PV generation helps supplement part of the power needed for heat pump solutions. Subsidy policies should emphasize deep renovation, ventilation heat recovery and onsite electricity generation.